SPDI The Total UV Solution
spdi, the total solution
 

 UV FAQs:

Technical Support: 561.243.8442

The answers in this section can generally be addressed to most common UV Systems. Please feel free to call Technical Support at SPDI if you have other UV Curing or Pre-treating questions.

  1. What if the UV doesn't cool quick enough to restart after 1 minute?
  2. What causes UV Lockout?
  3. What is UV Fault?
  4. What should the Current Relay be set at?
  5. What signal tells the machine that the UV is up to power and ready?
  6. How do you know if the cooling blower is working properly?
  7. How often should reflectors be cleaned/changed?
  8. How can you tell UV lamps need changed?
  9. What tells the system that the UV is cool enough to restart?
  10. What is the procedure to check the capacitors with a meter?
  11. What does the voltage sensing relay do? How do you know it's working properly?
  12. What is the pressure sensor relay?
  13. What does the lamp contactor do? How do you troubleshoot?
  14. System comes up to power then shuts down. What is the problem?
  15. The UV System tries to start, flashes and then shuts down. What do I look for?
  16. The UV lamps looked swelled and black on the ends, does this mean that they should be changed?
  17. Are all UV lamps of the same length the same wattage?
  18. UV comes up to full power but the machine doesn't start, the reflectors burn up and the wires get burnt to the lamps. What caused this?
 

1. What if the UV doesn't cool quick enough to restart after 1 minute?
A UV lamp has to be cool enough in order to be re-ignited. The amount of cooling a lamp gets after it has been shut down is usually controlled by a Cool Down Timer (or Blower Run On Timer). On some common UV Systems, this is labeled as T3. The Cool Down time should typically be around 60 seconds in order to allow, not only the lamp, but the electrical components within the irradiator enough time to adequately cool before a lamp re-start. If after this time the lamp has difficulty starting, check the blower filter to ensure that enough clean air is being allowed through to the lamp. Shortening the Cool Down time may allow the lamp to be started sooner after it has been powered down, but it may also allow excessive heat to build up within the irradiator and so damage the lamp leads or other components.

2. What causes UV Lockout?
A UV Lockout is when the UV System does not allow ignition of the UV Lamps. This can be during a warm up cycle, a cooldown cycle, or any other time the UV System deems unsafe to ignite the lamps. A UV Lockout on a MetalBox system is caused by the Lockout Relay (R1/R2) which is switched on when the Current Relays (CR1/CR2) do not detect any current draw after a lamp is ignited.

3. What is UV Fault?
UV Fault is caused when a lamp fails to ignite or fails to reach a ready condition. A UV Fault may have nothing to do with a lamp, but may be caused by some other component within the UV System.

4. What should the Current Relay be set at?
The Current Relay (CR1/CR2) should be set to between 1 and 5 amps. It is not too important as the relay is there just to sense current to see if the lamp is lit. After the lamp is ignited, the Lamp Start Timer has to expire to activate the Current Relay. This is to give the ignitor enough time to light the lamp. If the Current Relay does not read any current after this time, it is assumed that the lamp did not light.

5.What signal tells the machine that the UV is up to power and ready?
The Voltage Relays (VR1/VR2) signal the lamp has reached its normal operating voltage. This signal is used to start the cooling blower and to notify the printer. The normal operating voltage for a MetalBox lamp is anywhere between 250 and 310 volts, hence the Voltage Relay is normally set to the lower value.

6. How do you know if the cooling blower is working properly?
Most UV systems have some form of detector or switch that looks to see if the cooling blower is functioning. On a Metalbox system this takes the form of a pressure sensor in the UV irradiator. The pressure sensor is connected to the Cooling Pressure Switch Relay (labeled PR) that has to be enabled for the system to run. Although most systems can detect that the cooling blower is functioning, they cannot always tell you that you have enough or too much cooling. Regular inspection of the lamp is necessary to really ensure adequate cooling.

7. How often should reflectors be cleaned/changed?
Whenever the lamp is changed, or sooner if it is dirty/damaged. The importance of the reflector cannot be stressed enough, most of the curing power of the lamp comes from the reflected light.

8. How can you tell UV lamps need changed?
Over time the running voltage of a lamp will drop. Once the lamp falls beneath the voltage set be the Voltage Relay it will fail to send a Lamp ready signal to the Press. If a lamp becomes swollen due to overheating, this will also reduce the running voltage of the lamp. Swollen lamps will also not be as effective at curing. If all other components within the UV system are operating correctly, lamps should be changed when they fail to start, fail to reach ready, fail to cure, are too discolored or are swollen. 99% of lamp failures are normally misdiagnosed and are actually failures by other components in the system, such as capacitors, ballasts or ignitors.

9. What tells the system that the UV is cool enough to restart?
The Delay Start Timer (T2) is used to lock-out a re-start once the UV system is powered down.

10. What is the procedure to check the capacitors with a meter?

  • Disconnect all wires from the capacitor terminals.
  • Short the two terminals using a screwdriver with an insulated handle.
  • Connect the meter to the terminals and take reading. Replace the capacitor if the reading is 10% or more below the capacitors' value.

11. What does the voltage sensing relay do?
How do you know it's working properly? The Voltage Sensing Relays (VR1/VR2) are used to indicate when a lamp has reached its operating voltage (its ‘Ready Condition'), which in turn is used to start the cooling blower system. MetalBox 426 lamps normally run at a voltage between 250 and 320 volts (each lamp is slightly different). The Voltage Sensing Relay is normally set to the lower end of this range, typically 240-250 volts. See question 18 to find out what happens if the voltage relay does not work correctly.

12. What is the pressure sensor relay?
The pressure sensor relay is used to indicate that the irradiator is pressurized, ie. that the air from the cooling blower is reaching the irradiator. This is to verify that there is no problems between the blower and the irradiator, such as a damaged or blocked hose, or a choked blower air filter.

13. What does the lamp contactor do? How do you troubleshoot?
The Lamp Contactor (C2/C3) allows power to flow to the lamps, via the ballasts, capacitors and ignitors. In essence, these switch on the lamp circuits. The contactors themselves are energized by a control signal from the printers' PLC. A contactor, when engaged, should have the same voltage coming out as is going in, and should remain closed when the control signal is applied. A faulty contactor may ‘rattle' when it is energized and so turn the output voltage on and off very rapidly. This could cause spikes in the voltage and damage other components further down the line. A contactor can normally be pushed in by a screwdriver in order to turn it on, rather than be energized by a control voltage. This is useful when manual control is needed, for example to test the contactors output voltage or to briefly test the lamp's circuit.

14. System comes up to power then shuts down. What is the problem? Depending upon how far up to power the system was at the time it shut down, could be because one of the lamps failed to reach a ready status. If Lamp 1 ignited and then shut down, it will be because lamp 1 did not achieve ready. Lamp 2 will not ignite until Lamp 1 is ready. If Lamp 2 ignited, then we know already that Lamp 1 is running OK, but if Lamp 2 does not reach its ready condition, a UV Fault will be caused and both lamps will power down. The time a lamp is allowed to reach its ready condition from when it is ignited, is controlled from the PLC.

Alternatively, if Lamp 1 reached its ready condition and then the system went down, it could also be caused by a blower fault indicated by the Cooling Pressure Switch Relay (PR), or by the Current Relay for Lamp 2 (CR2) not detecting any current in Lamp 2 once it has been told to ignite.


15. The UV System tries to start, flashes and then shuts down. What do I look for? Check cables, caps, contactor (Lamp Contactor C2/C3), ballast and ignitor. Cables should be secure, capacitors should be within 8% of nominal, contactor should hold in when energized (and have the correct voltage coming out as was going in), and the ballast should output close to the same voltage that was input. There are easy steps to follow for checking capacitors and ballasts (if in doubt, call for more info), but the best way to check an ignitor is just to replace it with a new one.

16. The UV lamps looked swelled and black on the ends, does this mean that they should be changed?
Swelled and blackened lamps are a sign of overheating. If this is caught very early on, the blower baffle can be adjusted to allow for more cooling (or even clean filters installed on the cooling blower), and some use may still be squeezed out of the lamps. But generally once a lamp starts to swell, it can lose some of its curing properties, as well as drop in voltage. This drop in voltage may not allow the lamp to achieve its ready condition and so make the lamp more prone to failure.

17. Are all UV lamps of the same length the same wattage?
No. The power output of the lamp has nothing to do with its length, other factors such as the amount of mercury in the lamp and the power supply that feeds the lamp govern this. For example SPDI produce a variety of lamps which have a 6 inch arc length, but they vary from just a couple of hundred Watts Per Inch to over 1500.

18. UV comes up to full power but the machine doesn't start, the reflectors burn up and the wires get burnt to the lamps. What caused this?
It sounds as if the Voltage Sensing Relay is not working correctly or is set too high. The Voltage Sensing is used to indicate a Lamps ready status which is used to start the cooling blower and indicate to the press to start running. If the Voltage Sensing Relay never kicks on, the blower will not start and so the lamp will continue to heat up, and the press will never get the signal to start. Obviously an un-cooled lamp will damage anything within and near the irradiator, including reflectors, cables, junction boxes and the lamps.

 

Home | Our Company | Germicidal UV | UV Curing Systems | UV Lamps, Reflectors & More | Coatings & Finishes | Contact Us